Mismatch of overcurrent setting values: The overcurrent setting value of the upper-level circuit breaker is too small, or the overcurrent setting value of the lower-level circuit breaker is too large, resulting in that when the fault current occurs, the upper-level circuit breaker reaches the tripping condition first, while the lower-level circuit breaker does not act. For example, the overcurrent setting value of the UPS input main circuit breaker is set to 50A, while the overcurrent setting value of the load branch circuit breaker (with a rated current of 30A) is set to 60A. When the load branch has an overcurrent fault of 55A, the upper-level circuit breaker will trip first, resulting in overstep tripping.
Mismatch of tripping time setting: The tripping time of the upper-level circuit breaker is too short, or the tripping time of the lower-level circuit breaker is too long, which cannot form an effective time difference. High-frequency UPS has a fast response speed, and the fault current rises rapidly. If the upper-level circuit breaker adopts an instantaneous tripping mode (tripping time ≤0.1s) and the lower-level circuit breaker adopts a delayed tripping mode (tripping time ≥0.5s), when a short-circuit fault occurs, the upper-level circuit breaker will trip instantly before the lower-level circuit breaker acts, resulting in overstep tripping.
Incorrect selection of circuit breaker type: The upper-level and lower-level circuit breakers adopt inconsistent tripping characteristics (such as the upper-level adopts C-type tripping, and the lower-level adopts D-type tripping). C-type circuit breakers are suitable for resistive loads, with a tripping current of 5-10 times the rated current; D-type circuit breakers are suitable for inductive loads, with a tripping current of 10-20 times the rated current. If the selection is incorrect, the tripping sensitivity of the circuit breaker will be mismatched, leading to overstep tripping.
Fault of rectifier module: The rectifier module of high-frequency UPS is responsible for converting AC power into DC power to charge the battery and supply power to the inverter. If the rectifier module is faulty (such as IGBT module damage, rectifier bridge breakdown), it will cause the input current to be abnormal (such as current distortion, overcurrent), and the input main circuit breaker will trip first because it cannot be protected by the internal protection of the rectifier, resulting in overstep tripping.
Fault of inverter module: The inverter module converts DC power into stable AC power to supply power to the load. If the inverter module fails (such as IGBT short circuit, drive circuit failure), it will cause the output current to surge, and the internal protection switch of the inverter may fail to act in time due to damage or poor sensitivity, resulting in the upper-level circuit breaker tripping.
Abnormality of battery pack: The battery pack is the backup power source of UPS. If the battery pack has problems such as short circuit, leakage, or serious inconsistency of single-cell voltage, it will cause abnormal charging and discharging current when the UPS is in battery mode. For example, when the battery pack is short-circuited, the discharge current will exceed the rated current of the internal protection switch of UPS, and if the internal protection switch does not trip in time, the upper-level circuit breaker will trip to protect the system.
Failure of internal protection device: The high-frequency UPS is equipped with internal protection devices such as overcurrent protection, short-circuit protection, and over-temperature protection. If these protection devices fail (such as protection chip damage, signal transmission failure), they cannot detect the fault in time or issue a tripping command, resulting in the upper-level circuit breaker having to trip to cut off the fault current, leading to overstep tripping.
Unreasonable load distribution: The load connected to the high-frequency UPS is too concentrated, or the load capacity exceeds the rated capacity of the lower-level circuit breaker. For example, multiple high-power inductive loads (such as air conditioners, motors) are connected to a single load branch, which will cause a large inrush current when starting, and the lower-level circuit breaker cannot bear the inrush current, leading to the upper-level circuit breaker tripping first.
Excessive line impedance: The wiring of the load branch is too long, the cross-sectional area of the cable is too small, or the connection point is loose, resulting in excessive line impedance. When the load is working normally, the line voltage drop is too large, and the current is abnormal; when a fault occurs, the fault current cannot reach the tripping setting value of the lower-level circuit breaker in time, but the upper-level circuit breaker detects the abnormal current and trips first.
Incorrect grounding design: The grounding system of the high-frequency UPS is not standardized, such as poor grounding, mixed grounding of strong and weak electricity, or ground potential counterattack. When a fault occurs (such as leakage fault), the ground current is abnormal, which will cause the upper-level leakage circuit breaker to trip, resulting in overstep tripping.
Lack of surge protection: The high-frequency UPS system is not equipped with a surge protector (SPD) or the SPD fails. When the grid has a surge voltage or lightning strike, the transient overcurrent will enter the system, and the internal protection device of UPS cannot suppress it in time, leading to the upper-level circuit breaker tripping.
Grid abnormality: The grid voltage is too high or too low, voltage fluctuation, frequency deviation, or grid short circuit. For example, when the grid voltage drops sharply, the rectifier module of the high-frequency UPS will increase the input current to maintain the stable output of the system. If the input current exceeds the overcurrent setting value of the upper-level circuit breaker, the upper-level circuit breaker will trip.
Load abnormality: The load has faults such as short circuit, overload, or insulation damage. For example, the load insulation is damaged, resulting in leakage current. If the leakage current exceeds the setting value of the upper-level leakage circuit breaker, the upper-level circuit breaker will trip first; if the load is overloaded for a long time, the lower-level circuit breaker may be damaged and fail to act, leading to the upper-level circuit breaker tripping.
Large inrush current of load: When the high-frequency UPS supplies power to inductive loads (such as motors, transformers) or capacitive loads, a large inrush current will be generated when the load is started. If the inrush current exceeds the instantaneous tripping setting value of the upper-level circuit breaker, the upper-level circuit breaker will trip instantly, resulting in overstep tripping.
Harsh environmental conditions: The high-frequency UPS operates in an environment with high temperature, high humidity, high dust, or strong electromagnetic interference. High temperature will reduce the performance of electronic components and protection devices; high humidity will cause insulation damage and leakage; high dust will block the heat dissipation channel, leading to overheating of components; strong electromagnetic interference will affect the normal operation of the protection circuit, resulting in misoperation or failure of the protection device.
Neglect of operation and maintenance: The daily operation and maintenance of the high-frequency UPS system is not in place, such as not regularly checking the circuit breaker, not calibrating the protection setting value, not cleaning the components, and not replacing the aged components in time. These will lead to the decline of the performance of the protection device, the increase of contact resistance of the connection point, and the abnormal operation of the system, which will trigger overstep tripping when a fault occurs.
Fault phenomenon: Record which circuit breaker tripped (upper-level or lower-level), the tripping time, whether there is a fault prompt on the UPS panel (such as overcurrent, short circuit, over-temperature), and whether the load is working normally before the fault.
System parameters: Check the rated capacity of the UPS, the model and specification of each level of circuit breaker, the protection setting value (overcurrent setting, tripping time), the load distribution, and the wiring mode.
Operation records: Check the system operation records, including the grid voltage and current before the fault, the load current, the working mode of the UPS (grid mode or battery mode), and whether there is a surge, lightning strike, or load startup before the fault.
Environmental conditions: Record the temperature, humidity, and dust condition of the UPS room when the fault occurs, and whether there is electromagnetic interference nearby.
Check the circuit breaker: Check whether each level of circuit breaker is damaged, whether the contact is good, and whether the tripping mechanism is normal. Try to reset the tripping circuit breaker. If it trips again immediately, it indicates that there is a serious fault in the system (such as short circuit).
Check the load: Disconnect all loads, reset the circuit breaker, and observe whether the UPS can start normally. If it starts normally, it indicates that the fault is caused by the load (such as load short circuit, overload). Then connect the loads one by one to find the faulty load.
Check the grid: Use a multimeter to measure the grid voltage and frequency to see if they are within the normal range (generally AC 220V±10%, 50Hz±1%). If the grid is abnormal, it indicates that the fault may be caused by grid fluctuation.
Check the wiring: Check whether the wiring of the input and output circuits of the UPS is loose, whether the cable is damaged, and whether the cross-sectional area of the cable meets the requirements. If the wiring is loose, re-tighten it; if the cable is damaged, replace it in time.
Check the internal components of UPS: Disconnect the power supply of the UPS, open the cabinet door, check whether the rectifier module, inverter module, battery pack, and other components are damaged (such as bulging, burning, leakage), and use a multimeter to measure the resistance and voltage of the components to judge whether they are normal.
Check the protection setting value: Calibrate the overcurrent setting value and tripping time of each level of circuit breaker to see if they are consistent with the design requirements, and whether there is a mismatch between upper and lower levels. If the setting value is incorrect, adjust it according to the design standard.
Check the internal protection circuit: Check whether the protection chip, sensor, and signal transmission circuit of the UPS are normal, and simulate the fault signal to test whether the internal protection device can act normally.
Test the system current: Use a clamp ammeter to measure the input and output current of the UPS, the current of each load branch, and observe whether there is abnormal current (such as current distortion, overcurrent, leakage) to find the fault point.
For the mismatch of protection setting values: Adjust the overcurrent setting value and tripping time of each level of circuit breaker to ensure that there is a reasonable current difference and time difference between upper and lower levels. Generally, the overcurrent setting value of the upper-level circuit breaker should be 1.2-1.5 times that of the lower-level circuit breaker, and the tripping time should be 0.3-0.5s longer than that of the lower-level circuit breaker. At the same time, select the appropriate circuit breaker type according to the load characteristics.
For the abnormal operation of internal components: Replace the damaged rectifier module, inverter module, battery pack, and other components in time; repair the faulty internal protection device, and calibrate the protection chip and sensor to ensure their normal operation.
For unreasonable system design and wiring: Re-optimize the load distribution, avoid excessive load concentration, and ensure that the load capacity of each branch does not exceed the rated capacity of the lower-level circuit breaker; replace the cable with insufficient cross-sectional area, shorten the wiring length, and re-tighten the loose connection point; standardize the grounding system, separate the strong and weak electricity grounding, and ensure good grounding; install or replace the failed SPD to enhance the surge protection capability of the system.
For abnormal grid and load conditions: Coordinate with the power supply department to solve the grid abnormality; eliminate the load fault (such as repair the short-circuited load, reduce the load capacity), and install a soft starter for the load with large inrush current to suppress the inrush current.
For environmental factors and operation and maintenance neglect: Improve the operating environment of the UPS, install air conditioning, dehumidifier, and dust-proof equipment to ensure that the temperature is 15-25℃ and the humidity is 40%-60%; strengthen daily operation and maintenance, regularly check the circuit breaker, calibrate the protection setting value, clean the components, and replace the aged components in time.
Standardize system design: When designing the high-frequency UPS power supply system, strictly follow the relevant national standards and manufacturer's technical requirements, reasonably select the circuit breaker and cable, set the protection setting value scientifically, and ensure the selectivity of the hierarchical protection system. Conduct a comprehensive design review before the system is put into use to eliminate design hidden dangers.
Strengthen daily operation and maintenance: Establish a perfect operation and maintenance system, formulate a regular inspection plan, check the UPS system, circuit breaker, load, and wiring regularly, record the operation parameters, and find and eliminate hidden dangers in time. Regularly calibrate the protection setting value of the circuit breaker and the internal protection device of the UPS to ensure their accuracy and sensitivity.
Improve the surge and lightning protection capability: Install SPD at the input and output ends of the UPS, as well as the load branch, and regularly check the performance of the SPD to ensure that it can effectively suppress the surge voltage and lightning current. Standardize the grounding system to improve the anti-interference and anti-leakage capability of the system.
Strengthen load management: Reasonably arrange the load, avoid overload operation, and separate the inductive load, capacitive load, and resistive load to reduce the impact of inrush current. Regularly check the load equipment to ensure its normal operation, and avoid load faults causing system overstep tripping.
Train operation and maintenance personnel: Strengthen the professional training of operation and maintenance personnel, improve their ability to judge and handle faults, and ensure that when overstep tripping occurs, they can quickly find the fault point and take effective handling measures to minimize the impact of the fault.